Standard Profile Glass Insulators Manufacturer in China
Standard Profile Glass Insulators are designed to provide reliable insulation and mechanical support in high-voltage transmission and distribution systems. Manufactured from toughened glass, these insulators effectively prevent current leakage and ensure stable power delivery even under challenging outdoor conditions.
Our standard profile insulators can be supplied in a wide range of ratings and configurations to suit different line designs, voltage levels, and mechanical load requirements. In addition to their strong dielectric properties, they feature smooth surfaces that minimize pollution build-up, excellent resistance to aging, and consistent performance over decades of service.
| Basic Type | Figure No. | Minimum Mechanical Failing Load(kn) | Nominal Diameter d(mm) | Nominal Spacing p(mm) | Nominal Creepage Distance (mm) | Standard Coupling | Wet Power Frequency Withstand Voltage (kv) | Dry Lightning Impulse Withstand Voltage (kv) | Power Frequency Puncture Voltage (kv) | Radio Interference Voltage (μ v) 10kv 1mhz | Corona Visual Test p/c kv | Power Frequency Electric Arc Voltage | Impulse Puncture Voltage (p.u) | Net Weight (kg) |
| CTV175 (u40b) | 1-3 | 40 | 178 | 110 | 190 | 11 | 25 | 50 | 90 | 50 | 18/22 | 0.12s/20ka | 2.8 | 2.1 |
| CTV254 (u70b) | 1-3 | 70 | 255 | 127 | 320 | 16 | 40 | 100 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 3.5 |
| u70bl | 1-3 | 70 | 255 | 146 | 320 | 16 | 40 | 100 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 3.6 |
| u100bs | 1-3 | 100 | 255 | 146 | 320 | 16 | 40 | 100 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 4 |
| u120b | 1-3 | 120 | 255 | 146 | 400 | 16 | 40 | 100 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 4 |
| u160bs | 1-3 | 160 | 280 | 146 | 400 | 20 | 45 | 110 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 6.5 |
| u160bm | 1-3 | 160 | 280 | 155 | 400 | 20 | 45 | 110 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 6.6 |
| u160bl | 1-3 | 160 | 280 | 170 | 400 | 20 | 45 | 110 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 6.7 |
| u210b | 1-3 | 210 | 280 | 170 | 400 | 20 | 45 | 110 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 7.2 |
| u240b | 1-3 | 240 | 280 | 170 | 400 | 20/24 | 45 | 110 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 7.2 |
| u300b | 1-3 | 300 | 320 | 195 | 485 | 24 | 50 | 130 | 130 | 50 | 18/22 | 0.12s/20ka | 2.8 | 10.6 |
| u420b | 1-3 | 420 | 360 | 205 | 550 | 28 | 80 | 140 | 140 | 50 | 18/22 | 0.12s/20ka | 2.8 | 16 |
| u550b | 1-3 | 550 | 380 | 240 | 600 | 32 | 55 | 140 | 140 | 50 | 18/22 | 0.12s/20ka | 2.8 | 21.5 |
| Note: 1. the glass insulator model is in accordance with gb/t 7253-2005 and jb/t 9683-2012 (iec60305:1995, mod). the 420kn strength grade product contains 400kn strength grade, and the 550kn strength grade product contains 530kn strength grade.2. the connection structure is in accordance with gb/t 4056-2008 (iec60120: 1984, mod) and bs 3288 part3. according to the customer’s request, the locking pin can be w-pin or r-pin. unless otherwise specified, u70~u120 adopts w pin, and other uses r pin. | ||||||||||||||
Standard Profile Glass Insulators
Standard Profile Glass Insulators Features
Standard profile glass insulators are manufactured from high-quality toughened glass, offering excellent mechanical strength, thermal stability, and electrical performance. Their smooth glass surface minimizes the accumulation of dust and pollution, reducing leakage current and ensuring consistent insulation even in varied weather conditions. The transparency of glass provides a natural advantage, allowing operators to visually detect cracks or internal defects easily, which reduces the need for complex inspection methods. These insulators have a long service life, low maintenance requirements, and resistance to aging, corrosion, and ultraviolet radiation. Designed with high reliability, they ensure consistent performance across a wide range of operating voltages.


Standard Profile Glass Insulators Applications
Standard profile glass insulators are widely applied in medium- and high-voltage transmission and distribution networks, substations, and overhead power projects. They are suitable for use in regions with normal or moderately polluted environments where reliable insulation and mechanical strength are required. By securing conductors and preventing electrical breakdowns, they play a vital role in ensuring safe and efficient energy delivery across long distances. Their durability and cost-effectiveness make them a preferred choice for utilities worldwide, particularly in standard grid environments where long-term stability and low maintenance are priorities.
Exhibition & Shipment About Standard Profile Glass Insulators


Standard profile glass insulators are crafted from toughened glass, providing exceptional dielectric strength and mechanical resistance. Their classic bell shape is engineered to increase the surface creepage distance, preventing electrical flashovers, while their transparency allows for easy visual inspection for internal defects. A key safety feature is their tendency to shatter upon failure, offering a clear signal for replacement. These insulators are the workhorses of electrical grids, most commonly assembled into strings to support conductors on high-voltage transmission and distribution towers . They are also essential within substations for insulating busbars and equipment, and are frequently used in railway electrification due to their reliable all-around performance in areas with low to moderate pollution levels.
1.Portland Cement
Widely used for standard insulators.
Offers good strength and adhesion but may require additives to improve performance in high-voltage applications.
2.High Alumina Cement (HAC)
Very common in glass insulator manufacturing.
Provides high mechanical strength, excellent thermal resistance, and low shrinkage.
Better resistance to moisture and chemical attack compared to Portland cement.
3.Silica Cement
Sometimes used for bonding due to good thermal stability.
Offers a reliable bond with glass but is less common than alumina-based cements.
4.Special Modified Cements (Proprietary Blends)
Developed specifically by insulator manufacturers.
Usually based on alumina cement + additives to optimize expansion, adhesion, and durability.
Designed to withstand pollution, salt spray, and high voltage stresses.
In practice, High Alumina Cement (HAC) and its modified formulations are the most widely used for high-voltage glass insulators, as they balance mechanical strength, thermal compatibility, and long-term durability.